MECH3430 Fire Protection in Buildings - Worked Example for Design Considerations and Calculations for FHHR System in Sample Building.
MECH3430 Phòng cháy chữa cháy trong các tòa nhà - Ví dụ thực tế về các cân nhắc thiết kế và tính toán cho hệ thống FHHR trong tòa nhà mẫu.
1. Information of the Sample Building
• Commercial building – 500m2 for each floor
• 20 storeys (G/F, 1 -20/F, Roof), 4m height floor-to-floor, no refuge floor
• 2 staircases with FH in both staircases
• 2 HR for each floor and each one is located near one of the escape staircases
• FS Tank at roof level
• Available pump locations: G/F and Roof
2. Legislative Requirements
Definition of ‘High-rise’ – any building of which the floor of the uppermost
storey exceeds 30m above the point of staircase discharge at ground floor level
(in this Sample building, uppermost storey > 30m)
Section 4.15 of CoP FSI – Commercial buildings – high-rise
(x) fire hydrant / hose reel system
EXTENT
There shall be sufficient hydrants and hose reels on each floor to ensure that every
part of the building can be reached by a length of not more than 30m of Fire
Services hose and hose reel tubing
Section 5.14 of CoP FSI – Fire hydrant / hose reel system
(d) Fixed Fire Pump
LINK 3 - TÌM KIẾM SÁCH/TÀI LIỆU ONLINE (GIÁ ƯU ĐÃI NHẤT)
LINK 4 - TÌM KIẾM SÁCH/TÀI LIỆU ONLINE (GIÁ ƯU ĐÃI NHẤT)
MECH3430 Phòng cháy chữa cháy trong các tòa nhà - Ví dụ thực tế về các cân nhắc thiết kế và tính toán cho hệ thống FHHR trong tòa nhà mẫu.
1. Information of the Sample Building
• Commercial building – 500m2 for each floor
• 20 storeys (G/F, 1 -20/F, Roof), 4m height floor-to-floor, no refuge floor
• 2 staircases with FH in both staircases
• 2 HR for each floor and each one is located near one of the escape staircases
• FS Tank at roof level
• Available pump locations: G/F and Roof
2. Legislative Requirements
Definition of ‘High-rise’ – any building of which the floor of the uppermost
storey exceeds 30m above the point of staircase discharge at ground floor level
(in this Sample building, uppermost storey > 30m)
Section 4.15 of CoP FSI – Commercial buildings – high-rise
(x) fire hydrant / hose reel system
EXTENT
There shall be sufficient hydrants and hose reels on each floor to ensure that every
part of the building can be reached by a length of not more than 30m of Fire
Services hose and hose reel tubing
Section 5.14 of CoP FSI – Fire hydrant / hose reel system
(d) Fixed Fire Pump