TÀI LIỆU BỘ ĐIỀU KHIỂN MÁY PHÁT ĐIỆN CUMMINS - Generator Sets Controller T210 Operation Manual



Section 3 Specifications 

Power Source

„  8V-36V DC 

„  Consumption: 0.1A-0.4Ačat 24VĎ

Environment

„  Storage temperatureğ-30¥~+80¥

„  Operating temperatureğ-20¥~+70¥

„  Humidityğ90%RH Max at 40¥

Dimensions

„  Width: 200mm 

„  Height: 100mm 

„  Depth: 4 7mm 

Weight 

„  1.0kg

Generator Related 

„  Nominalfrequencyğ50-60Hz 

„  Frequency measurement toleranceğ0.1Hz 

„  Max. measured voltage: 

ƒ  290V (phase to neutral)

ƒ  400V(phase to phase) 

„  Voltage measurement toleranceğ2%č220VĎ

„  Rated input current (from CT)ğ5A 

„  Current measurement toleranceğ2%č5AĎ

Binary Inputs

„  Input resistance: 4.7kΩ

„  Low voltage levelfor active indicationğ0-2V 

„  High voltagelevelfor de-active indicationğ8-36V 

Open Collector Outputs 

„  Max. currentğ0.5A 

„  Max. switching voltageğ36V 

Relay Outputs 

„  Max. currentğ

„  10A resistive load 

14 

„  3A inductiveload 

„  Max. switching voltageğ36V 

Analog Inputs

„  Resolution: 10bits 

„  Sensor resistor range: 0-2.4kΩ

Speed Sensor Inputs 

„  Type of Sensor: Magnetic pick-up 

„  Min. Input Voltage: 2Vpk-pk(4Hz to 4kHz) 

„  Max. Input Voltage: 50V 

„  Frequency measurement rang: 4Hz-10kHz


Appendix B. Alarm Event 

Event  Description

fail-stop stop

Stopping sequence activated when unsuccessfulGenerator

sets Stop happening 

emerg stop  Emergency stop activated 

o.p. sw alm  Oilpressure switch alarm 

w.t. sw alm  Coolant temperature switch alarm 

f.l. sw alm  Fuellevelswitch alarm 

o.p. sen. Pre_alm Oilpressure sensor pre-alarm under “O.P. Lev1” set point) 

o.p. sen alm  Oilpressure sensor alarm(under “O.P. Lev2” set point) 

w.t. sen. Pre-alm 

Coolant temperature sensor pre-alarm(above “W.T. Lev1” set 

point) 

w.t. sen. alm 

Coolant temperature sensor pre-alarm (above “W.T. Lev1” set 

point) 

f.l. sen. Pre-alm  Fuellevelsensor pre-alarm(under “F.L. Lev1” set point) 

f.l. sen. alm  Fuellevelsensor alarm(under “F.L. Lev2” set point) 

high batt  High battery voltage alarm(above “Batt>V” set point) 

low batt  Low battery voltage alarm(under “Batt<V” set point) 

v-batt understop  Generator sets stopby battery alarm 

gen freq alm  Generator frequency alarm 

vg1 alm  Generator phase 1 voltage alarm 

vg2 alm  Generator phase 2 voltage alarm 

vg3 alm  Generator phase 3 voltage alarm 

gen-failstop  Generator voltage not present inMaxStab state

igunbal  Generator current unbalance 

vg unbalalm  Generator voltage unbalance 

ig-short  Generator current over “Curr Short” set point 

ig-over  Generator current over “Curr Over” set point 

active power over Generator active power over “Curr Over” set point

under-speed stop Generator set under speed stop 

over-speed stop  Generator set over speed stop 

start-failstop  Generator set continued start failat AUTO mode

pm hours arrival  Generator set preventive maintenance hours is overtime


LINK DOWNLOAD



Section 3 Specifications 

Power Source

„  8V-36V DC 

„  Consumption: 0.1A-0.4Ačat 24VĎ

Environment

„  Storage temperatureğ-30¥~+80¥

„  Operating temperatureğ-20¥~+70¥

„  Humidityğ90%RH Max at 40¥

Dimensions

„  Width: 200mm 

„  Height: 100mm 

„  Depth: 4 7mm 

Weight 

„  1.0kg

Generator Related 

„  Nominalfrequencyğ50-60Hz 

„  Frequency measurement toleranceğ0.1Hz 

„  Max. measured voltage: 

ƒ  290V (phase to neutral)

ƒ  400V(phase to phase) 

„  Voltage measurement toleranceğ2%č220VĎ

„  Rated input current (from CT)ğ5A 

„  Current measurement toleranceğ2%č5AĎ

Binary Inputs

„  Input resistance: 4.7kΩ

„  Low voltage levelfor active indicationğ0-2V 

„  High voltagelevelfor de-active indicationğ8-36V 

Open Collector Outputs 

„  Max. currentğ0.5A 

„  Max. switching voltageğ36V 

Relay Outputs 

„  Max. currentğ

„  10A resistive load 

14 

„  3A inductiveload 

„  Max. switching voltageğ36V 

Analog Inputs

„  Resolution: 10bits 

„  Sensor resistor range: 0-2.4kΩ

Speed Sensor Inputs 

„  Type of Sensor: Magnetic pick-up 

„  Min. Input Voltage: 2Vpk-pk(4Hz to 4kHz) 

„  Max. Input Voltage: 50V 

„  Frequency measurement rang: 4Hz-10kHz


Appendix B. Alarm Event 

Event  Description

fail-stop stop

Stopping sequence activated when unsuccessfulGenerator

sets Stop happening 

emerg stop  Emergency stop activated 

o.p. sw alm  Oilpressure switch alarm 

w.t. sw alm  Coolant temperature switch alarm 

f.l. sw alm  Fuellevelswitch alarm 

o.p. sen. Pre_alm Oilpressure sensor pre-alarm under “O.P. Lev1” set point) 

o.p. sen alm  Oilpressure sensor alarm(under “O.P. Lev2” set point) 

w.t. sen. Pre-alm 

Coolant temperature sensor pre-alarm(above “W.T. Lev1” set 

point) 

w.t. sen. alm 

Coolant temperature sensor pre-alarm (above “W.T. Lev1” set 

point) 

f.l. sen. Pre-alm  Fuellevelsensor pre-alarm(under “F.L. Lev1” set point) 

f.l. sen. alm  Fuellevelsensor alarm(under “F.L. Lev2” set point) 

high batt  High battery voltage alarm(above “Batt>V” set point) 

low batt  Low battery voltage alarm(under “Batt<V” set point) 

v-batt understop  Generator sets stopby battery alarm 

gen freq alm  Generator frequency alarm 

vg1 alm  Generator phase 1 voltage alarm 

vg2 alm  Generator phase 2 voltage alarm 

vg3 alm  Generator phase 3 voltage alarm 

gen-failstop  Generator voltage not present inMaxStab state

igunbal  Generator current unbalance 

vg unbalalm  Generator voltage unbalance 

ig-short  Generator current over “Curr Short” set point 

ig-over  Generator current over “Curr Over” set point 

active power over Generator active power over “Curr Over” set point

under-speed stop Generator set under speed stop 

over-speed stop  Generator set over speed stop 

start-failstop  Generator set continued start failat AUTO mode

pm hours arrival  Generator set preventive maintenance hours is overtime